Showing posts with label Network anaysis. Show all posts
Showing posts with label Network anaysis. Show all posts

Tuesday, January 17, 2012

Balanced Three phase AC circuit Delta connected

A balanced three phase AC circuit systems is energized by three equal alternating emf's of the same frequency but 120 degree apart. The phase impedance are equal. Also the currents are equal and 120 degree apart.
Three AC emf's differing in time phase by 120 degree
Three AC emf's differing in time phase by 120 degree
DELTA (MESH) CONNECTED SYSTEM
This type of connection is reffered to as 3 phase, 3 wire system. In this connection , the dissimilar ends of the 3 phase windings of a 3 phase ac generator are joined together,  for example the starting ends of one phase is joined to finishing end of the other phase so on. In other words the three winding's are joined in series to form a closed mesh. three leads are taken out from the juntions to serve as the generator terminals.
Delta mesh connected system
Delta connected System
Relationships: VØ = VL       :  IØ = IL/(3)   
 Where:
        VØ  - phase voltage
        IØ  - phase current
       VL -  line voltage
       IL -  line voltage

The three phase voltages of this circuit always sum to zero  Va + Vb + Vc =0

As seen from the diaram, there is only one phase winding completely included between any pair of terminals. Hence, in delta connection, the voltage between any pair of lines is equal of the phase voltage of the phase winding connected between the two lines considered.

Friday, December 10, 2010

Power Factor for a more efficient circuit and loading

Power factor is an important aspect to consider in AC circuit, because any factor less than 1 means that the circuit wiring has to carry more current than what would be necessary with zero reactance in the circuit to deliver the same true power to the resistive load.
    When expressed as fraction, the ratio between true power and  apparent power is called the power factor of the circuit.
                                                     Kw
The power factor is given cosƟ = --------
                                                    KVA
in the case of single phase supply

                     VI                    KVAx1000
KVA=     ----------  or I=    -----------  
                     1000                    V

In case of three-phase supply
            sqrt(3)VL IL                 KVAx 1000
KVA= --------------     or IL=-------------
                1000                           sqrt(3)VL
In the case of three phase supply
   All current will cause losses in the supply and distribution system. A load with a power of 1.0 result in the most efficient loading of the supply and a load with a power of 0.5 will result in much higher losses in the supply such as an induction motor, power transformer, lighting ballast,welder or variable speed drive, switched mode power supply, discharge lighting or other electronic load.
  The heating and lighting loads supplied from three-phase supply have power factors ranging from 0.95 to unity. But motor loads have usually low lagging power factor ranging from 0.5 to 0.9. Single phase motors may have a power factor of as low as 0.4 and electric welding units have even lower power factor of 0.2 or 0.3
 A poor power factor due to an inductive load can be improved by the addition of power factor correction,but a poor power factor due to a distorted current waveform requires a change in equipment design or expensive harmonic filter s to gain an appreciable improvement. many inverters are quoted as having a power factor of better than 0.95 when in reality, true power factor is between 0.5 and 0.75. the Figure of 0.95 is based on the cosine of the angle between the voltage and current but does not take into account that the current waveform is discontinues and therefore contributes to increased losses on the supply
   in each  equation above, the KVA is directly proportional to the current. The chief disadvantage of a low power factor is that the current requires for a given power is very high. this fact leads to the following undesirable results.

1. Large KVA for a given amount of power.
    All electric machines such as alternators, transformers, cables are limited in their current-carrying capacity by the permissible temperature rise which is proportional to I^2 .hence, they may all be fully loaded with respect to their rated KVA without delivering their full power.

2. Poor voltage regulation . When loading a low lagging power factor is switched on,there is a large voltage drop in the supply lines and transformers. this drop in voltage adversely affects the starting torque of motors and needs expensive voltage stabilizing equipment for keeping the consumers voltage fluctuations within the statutory limits